DocumentCode
1395809
Title
Application of high voltage current limiting fuse model using ATP-draw
Author
Lee, Sei-Hyun
Author_Institution
Dept. of Electr. Meas. & Control Eng., Korea Polytech. Coll. 4, South Korea
Volume
17
Issue
6
fYear
2010
Firstpage
1806
Lastpage
1813
Abstract
This paper presents the results of arcing energy by the initiation of arcing, the arc clearing voltage, the system impedance (X/R), and the making angle. To perform this analysis, current limiting fuse (CLF) model was developed using the ATP-Draw program. The violent activation of arc is affected by the voltage level, the voltage rise rate when the arcing starts, and the minimum and the maximum positions of the arcing energy that can be moved to zero degree by the X/R, and the more severe interrupted condition has to be considered. The model developed using ATP-Draw enables a non-expert to use it without spending excessive time and effort.
Keywords
arcs (electric); electric fuses; fault current limiters; ATP-draw program; arc clearing voltage; arcing energy; current limiting fuse; making angle; system impedance; Circuit faults; Fault currents; Fuses; Immune system; Limiting; Mathematical model; Voltage control; Modeling, current limiting fuses, X/R, power factor, arcing energy, fault current, prospective current;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2010.5658232
Filename
5658232
Link To Document