DocumentCode :
1397961
Title :
3-D nonlinear transient electromagnetic analysis of short circuit electromagnetic forces in a three-phase enclosure-type gas insulated bus
Author :
Takeuchi, Toshie ; Yoshizawa, Toshiyuki ; Kuse, Yuko ; Hama, Hiroyuki
Author_Institution :
Adv. Technol. R&D Center, Mitsubishi Electr. Corp., Hyogo, Japan
Volume :
36
Issue :
4
fYear :
2000
fDate :
7/1/2000 12:00:00 AM
Firstpage :
1754
Lastpage :
1757
Abstract :
An accurate analysis of short circuit electromagnetic forces in a three-phase enclosure-type gas insulated bus (GIB) has been performed. The analysis clarified the effects of the eddy currents (skin effect) and the nonlinear permeability on the materials. The calculated magnetic fields agree with the measured fields. The electromagnetic force analysis considering the skin effect and the nonlinear permeability of the magnetic materials is important in view of reducing the GIB size
Keywords :
busbars; eddy currents; electromagnetic forces; finite element analysis; gaseous insulation; magnetic permeability; short-circuit currents; skin effect; substations; 3-D nonlinear transient electromagnetic analysis; 3D finite element methods; eddy currents; magnetic fields; nonlinear permeability; short circuit electromagnetic forces; skin effect; substations; three-phase enclosure-type gas insulated bus; Circuits; Electromagnetic analysis; Electromagnetic forces; Electromagnetic transients; Magnetic analysis; Magnetic field measurement; Magnetic materials; Permeability; Skin effect; Transient analysis;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/20.877783
Filename :
877783
Link To Document :
بازگشت