Abstract :
An accurate analysis of short circuit electromagnetic forces in a three-phase enclosure-type gas insulated bus (GIB) has been performed. The analysis clarified the effects of the eddy currents (skin effect) and the nonlinear permeability on the materials. The calculated magnetic fields agree with the measured fields. The electromagnetic force analysis considering the skin effect and the nonlinear permeability of the magnetic materials is important in view of reducing the GIB size
Keywords :
busbars; eddy currents; electromagnetic forces; finite element analysis; gaseous insulation; magnetic permeability; short-circuit currents; skin effect; substations; 3-D nonlinear transient electromagnetic analysis; 3D finite element methods; eddy currents; magnetic fields; nonlinear permeability; short circuit electromagnetic forces; skin effect; substations; three-phase enclosure-type gas insulated bus; Circuits; Electromagnetic analysis; Electromagnetic forces; Electromagnetic transients; Magnetic analysis; Magnetic field measurement; Magnetic materials; Permeability; Skin effect; Transient analysis;
Journal_Title :