Intermittent Line-to-Ground Faults in Generator Stator Windings and Consequences on Neutral Grounding
Author :
Braun, Dieter ; Koeppl, Georg S.
Author_Institution :
ABB Switzerland, Zurich, Switzerland
Volume :
25
Issue :
2
fYear :
2010
fDate :
4/1/2010 12:00:00 AM
Firstpage :
876
Lastpage :
881
Abstract :
Line-to-ground faults in the stator windings of unit generators have been simulated on the basis of test results obtained on medium-voltage cables in systems with isolated neutral. Those tests have shown that single-phase faults in insulating materials, such as polyethylene or comparable synthetics, are normally arcing faults and the arcing channel in the insulating material behaves like a restriking switch which is able to interrupt transient fault currents at current zero; however, it restrikes at a certain voltage level due to damaged insulation and small distances between the phase conductor and ground. Similar behavior may be assumed for generator stator windings. The simulations show that for such a fault pattern, resonant grounding is distinctly to be preferred to high resistance grounding. The corresponding standards do not reflect transient and intermittent fault currents in stator windings and, therefore, assess both grounding methods as nearly equivalent.
Keywords :
earthing; electric generators; fault currents; fault diagnosis; machine insulation; machine protection; stators; arcing channel; arcing faults; fault pattern; generator stator windings; grounding methods; high resistance grounding; intermittent line-to-ground faults; medium-voltage cables; neutral grounding; polyethylene synthetics; resonant grounding; Fault currents; grounding; synchronous generators; transient analysis;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2037967
Filename :
5406025
Link To Document :
بازگشت