    Impulse voltage tests on a 4.8-kv. distribution substation

  • Author

    Collins, H. W. ; Piepho, E. E. ; Torok, J. J.

  • Author_Institution
    Detroit Edison Co., Detroit, Mich.
  • Volume
    50
  • Issue
    11
  • fYear
    1931
  • Firstpage
    901
  • Lastpage
    901
  • Abstract
    DISTRIBUTION lines from ungrounded 4,800-volt substations of the Detroit Edison Company commonly have several hundred feet of three-phase underground cable between the overhead lines and the station, voltage regulators being connected between the bus and the station end of the cable. Although lightning arresters are connected at the substation bus and at the junctions of the overhead lines and entrance cables, a number of flashovers due to lightning voltage have occurred, consistently between the line terminal of the regulator and the station end of the entrance cable.