DocumentCode :
1406291
Title :
Discussion of "Fault-current limiter applications in medium- and high-voltage power distribution systems" [and reply]
Author :
Das, J.C. ; Wu, A.Y. ; Yuexin Yin
Author_Institution :
Simons Eng. Inc., Decatur, GA, USA
Volume :
34
Issue :
4
fYear :
1998
Firstpage :
638
Lastpage :
639
Abstract :
The author makes five comments on the paper by A.Y. Wu and Y. Yin (see ibid., vol.34, p.236-42, 1998). The author points out that there are no fault current limiters available for applications above 38 kV, discusses two sensing modes for current limiters, zero current crossings for fault currents, coordination between the current limiter and the phase overcurrent relays, and briefly mentions reactor bypass schemes. The original authors reply to the comments.
Keywords :
current limiters; fault currents; fault currents; fault-current limiter applications; high-voltage power distribution systems; medium-voltage power distribution systems; phase overcurrent relays; reactor bypass schemes; sensing modes; zero current crossings; Circuit faults; Delay effects; EMTP; Fault currents; Frequency; Medium voltage; Mirrors; Power distribution; Shape; Switchgear;