• DocumentCode
    1406803
  • Title

    A new approach to enhance power quality for medium voltage AC drives

  • Author

    Hammond, Peter W.

  • Author_Institution
    Robicon Corp., Pittsburgh, PA, USA
  • Volume
    33
  • Issue
    1
  • fYear
    1997
  • Firstpage
    202
  • Lastpage
    208
  • Abstract
    A new approach to medium-voltage variable-frequency static AC motor drives offers improvements in power quality. Harmonic current injection into the power lines is below the most severe requirements of IEEE Standard 519-1992. The power factor of this new type of drive exceeds 94% at full load and is above 90% at 10% load. Motor voltage and current waveforms are improved so that torque pulsations are reduced. Peak voltage stress on motor insulation does not exceed peak input line voltage, and no zero sequence voltage is imposed. Drive efficiency exceeds 96%. This paper describes the new approach and some of the results achieved
  • Keywords
    AC motor drives; IEEE standards; harmonic distortion; power factor; power supply quality; power system harmonics; IEEE Standard 519-1992; MV AC motor drives; current waveforms; harmonic current injection; motor insulation; peak input line voltage; peak voltage stress; power factor; power quality enhancement; torque pulsations; voltage waveforms; Chemical industry; Costs; Manufacturing; Medium voltage; Petroleum; Power system harmonics; Power transformer insulation; Pulse width modulation; Reactive power; Torque;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.567113
  • Filename
    567113