    Improved Starting Process Alternative to Conventional Star-Delta Switching of A-C Meters

  • Author

    Abdel-Hamid, M.N.

  • Author_Institution
    University of Cairo, Giza, Egypt.
  • Volume
    82
  • Issue
    65
  • fYear
    1963
  • fDate
    3/1/1963 12:00:00 AM
  • Firstpage
    52
  • Lastpage
    60
  • Abstract
    For the purpose of reducing mechanical shocks caused by the sudden increase of torque, and to avoid high current transients as a result of the interruption of supply in the conventional stardelta switching, an alternative starting process is presented here. It is proposed to start the motor on the unbalanced-delta connection in which a resistance is inserted in one of the lines feeding its delta-connected stator. When the running speed has been reached, the resistance is bridged to permit normal balanced running. It is also proposed to use the unbalanced-delta connection as an intermediate step in star-delta switching. In this respect, the once suggested open-delta connection is proved unsuitable for this purpose.