Stability experiences with conowingo hydro plant
Author
Hentz, R. A. ; Jones, J. W.
Author_Institution
Philadelphia (Pa.) Electric Company
Volume
51
Issue
2
fYear
1932
Firstpage
95
Lastpage
102
Abstract
During the first year of operation, four cases of instability developed at Conowingo hydroelectric station of the Philadelphia Electric Company when faults occurred on the transmission lines. Subsequent investigations showed that some of the generators would advance 180 deg. ahead of the system in less than 0.3 sec. when full load was dropped suddenly. Installation of higher speed relays and circuit breakers together with changes in the operating set-up, have corrected the situation.
Keywords
Circuit breakers; Circuit faults; Circuit stability; Companies; Generators; Relays; Stability analysis;