• DocumentCode
    1407002
  • Title

    Stability experiences with conowingo hydro plant

  • Author

    Hentz, R. A. ; Jones, J. W.

  • Author_Institution
    Philadelphia (Pa.) Electric Company
  • Volume
    51
  • Issue
    2
  • fYear
    1932
  • Firstpage
    95
  • Lastpage
    102
  • Abstract
    During the first year of operation, four cases of instability developed at Conowingo hydroelectric station of the Philadelphia Electric Company when faults occurred on the transmission lines. Subsequent investigations showed that some of the generators would advance 180 deg. ahead of the system in less than 0.3 sec. when full load was dropped suddenly. Installation of higher speed relays and circuit breakers together with changes in the operating set-up, have corrected the situation.
  • Keywords
    Circuit breakers; Circuit faults; Circuit stability; Companies; Generators; Relays; Stability analysis;