DocumentCode :
1407768
Title :
Impulse tests on a substation
Author :
Collins, H. W. ; Piepho, E. E. ; Torok, J. J.
Author_Institution :
Detroit Edison Co., Detroit, Michigan
Volume :
51
Issue :
5
fYear :
1932
fDate :
5/1/1932 12:00:00 AM
Firstpage :
304
Lastpage :
306
Abstract :
Severe flashovers have occurred in ungrounded 4,800-volt distribution substations in Detroit. Impulse tests have proved that these were caused by surges reflected from regulator windings, but can be prevented by the proper placing of lightning arresters.
Keywords :
Arresters; Lightning; Regulators; Substations; Surges; Voltage control; Wires;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1932.6429794
Filename :
6429794
Link To Document :
بازگشت