Title :
Factors affecting the results of 50 c/s wet flashover tests
Author :
Standring, W.G. ; Hughes, R.C. ; Roberts, W.J.
Volume :
110
Issue :
6
fYear :
1963
fDate :
6/1/1963 12:00:00 AM
Firstpage :
1072
Lastpage :
1076
Abstract :
The wet flashover voltage of an insulator depends partly on the angle at which the water-drops fall but mainly on the quantity of water striking the insulator. A visual estimate of the angle and a measurement of the vertical rate of fall does not give a satisfactory indication of the quantity striking the insulator if spiral nozzles are used. A suggestion is made to improve the consistency of wet-test results by using plain nozzles and by making two simple measurements of spray intensity.
Keywords :
electric breakdown; flashover; insulation testing; insulators;