Title :
Puncture risks when testing large synchronous machines with direct voltage
Author_Institution :
ASEA, Research Laboratories, Vÿsterås, Sweden
fDate :
9/1/1963 12:00:00 AM
Abstract :
The electrostatic field distribution is calculated for the insulation of the coil ends of a winding undergoing a direct-voltage test. It is found that a relatively high voltage can occur across the insulation of the coil ends if these are covered with a layer of dust or moisture, and a puncture may occur. By considering the effect of such a puncture upon the current in the test circuit, it is demonstrated that a puncture at some distance from the stator core may be left unnoticed. Such punctures have been discovered in coils subjected to field tests with direct voltage.
Keywords :
electric fields; insulation testing; machine windings; synchronous machines; testing;