DocumentCode
1412427
Title
Puncture risks when testing large synchronous machines with direct voltage
Author
Virsberg, L.G.
Author_Institution
ASEA, Research Laboratories, Vÿsterås, Sweden
Volume
110
Issue
9
fYear
1963
fDate
9/1/1963 12:00:00 AM
Firstpage
1637
Lastpage
1639
Abstract
The electrostatic field distribution is calculated for the insulation of the coil ends of a winding undergoing a direct-voltage test. It is found that a relatively high voltage can occur across the insulation of the coil ends if these are covered with a layer of dust or moisture, and a puncture may occur. By considering the effect of such a puncture upon the current in the test circuit, it is demonstrated that a puncture at some distance from the stator core may be left unnoticed. Such punctures have been discovered in coils subjected to field tests with direct voltage.
Keywords
electric fields; insulation testing; machine windings; synchronous machines; testing;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1963.0232