DocumentCode :
1412637
Title :
Performance of IEC 61850-9-2 Process Bus and Corrective Measure for Digital Relaying
Author :
Kanabar, Mitalkumar G. ; Sidhu, Tarlochan S.
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Western Ontario, London, ON, Canada
Volume :
26
Issue :
2
fYear :
2011
fDate :
4/1/2011 12:00:00 AM
Firstpage :
725
Lastpage :
735
Abstract :
International Electrotechnical Commission (IEC) standard 61850 proposes the Ethernet-based communication networks for protection and automation within the power substation. Major manufacturers are currently developing products for the process bus in compliance with IEC 61850 part 9-2. For the successful implementation of the IEC 61850-9-2 process bus, it is important to analyze the performance of time-critical messages for the substation protection and control functions. This paper presents the performance evaluation of the IEC 61850-9-2 process bus for a typical 345 kV/230 kV substation by studying the time-critical sampled value messages delay and loss by using the OPNET simulation tool in the first part of this paper. In the second part, this paper presents a corrective measure to address the issues with the several sampled value messages lost and/or delayed by proposing the sampled value estimation algorithm for any digital substation relaying. Finally, the proposed sampled value estimation algorithm has been examined for various power system scenarios with the help of PSCAD/EMTDC and MATLAB simulation tools.
Keywords :
IEC standards; local area networks; power system CAD; power system relaying; power system simulation; substation automation; substation protection; Ethernet-based communication networks; IEC 61850-9-2 process bus; International Electrotechnical Commission; MATLAB simulation tools; OPNET simulation tool; PSCAD/EMTDC; digital substation relaying; power substation automation; power substation protection; power system; voltage 230 kV; voltage 345 kV; Ethernet; IEC 61850; IEC 61850-9-2; generic object-oriented substation event (GOOSE); intelligent electronic device (IED); process bus; sampled values (SVs); substation automation system (SAS);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2038702
Filename :
5409526
Link To Document :
بازگشت