DocumentCode
1412875
Title
Transients in distance protection
Author
Mathews, P. ; Nellist, B.D.
Volume
110
Issue
2
fYear
1963
fDate
2/1/1963 12:00:00 AM
Firstpage
407
Lastpage
418
Abstract
The demand for high-speed operation in distance protection involves design consideration under three main headings, namely: the transient primary current and voltage at the relaying point; the modification of these signals due to secondary circuits; and the effect of the modified secondary signals on two input comparators currently or prospectively employed. These are considered in terms of simple formulation showing their effect on voltage transformers and current transducers (whether current transformers or linear couplers). Alternative means of eliminating, or equating, transient secondary current and voltage signals are considered. The use of secondary replica impedances is formulated, and the effect of the relaxation transient in the voltage-transformer secondary circuit and its relation to transient time delay are pointed out. General consideration is given to the effect of secondary transient signals, containing components of different time-constants determined, respectively, by the primary and the secondary circuits, and of unequal amplitude, on currently used comparators.
Keywords
protection; transients;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1963.0056
Filename
5247865
Link To Document