• DocumentCode
    1412954
  • Title

    Lightning experience with new transformer connection

  • Author

    Haines, T. H. ; Corney, C. A.

  • Author_Institution
    Edison Elec. Illum. Co. of Boston, Mass.
  • Volume
    52
  • Issue
    4
  • fYear
    1933
  • fDate
    4/1/1933 12:00:00 AM
  • Firstpage
    229
  • Lastpage
    232
  • Abstract
    Distribution transformers in several locations on a New England system have been operating for several months with the primary lightning arrester ground interconnected with the transformer secondary neutral. Experience over the past few months definitely indicates the advantages of this connection in reducing troubles due to lightning, without increasing the hazard to the customers´ wiring. Increased clearances on transformer primary bushings also reduce the number of failures.
  • Keywords
    Arresters; Cities and towns; Fuses; Insulators; Lightning; Oil insulation; Resistance;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1933.6430684
  • Filename
    6430684