DocumentCode :
1413017
Title :
Apparent core losses and core losses in five-limb amorphous transformer of 160 kVA
Author :
Sieradzki, Stefan ; Rygal, Roman ; Soinski, Marian
Author_Institution :
PPU EMITRA sc, Lubliniec, Poland
Volume :
34
Issue :
4
fYear :
1998
fDate :
7/1/1998 12:00:00 AM
Firstpage :
1189
Lastpage :
1191
Abstract :
Significant modifications of the shape of magnetic flux in columns and yokes were observed in the magnetic circuit of four amorphous cores used in a 3-phase transformer. The magnetic losses measured experimentally were significantly higher than the ones calculated theoretically. The values quoted in this paper were obtained in our study, and they are indicative of the need of taking them into consideration when designing 5-limb amorphous distribution transformers
Keywords :
losses; magnetic flux; magnetic leakage; power transformers; transformer cores; transformer magnetic circuits; 160 kVA; 3-phase transformer; 5-limb amorphous distribution transformers; apparent core losses; columns; core losses; five-limb amorphous transformer; magnetic circuit; magnetic flux shape; magnetic losses; yokes; Amorphous magnetic materials; Amorphous materials; Core loss; Loss measurement; Magnetic circuits; Magnetic cores; Magnetic flux; Magnetic losses; Shape; Transformer cores;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/20.706475
Filename :
706475
Link To Document :
بازگشت