    The effect of transient voltage protective devices on stresses in rower transformers

  • Author

    Palueff, K. K. ; Hagenguth, J. H.

  • Author_Institution
    General Electric Company, Pittsfield, Mass.
  • Volume
    52
  • Issue
    6
  • fYear
    1933
  • fDate
    6/1/1933 12:00:00 AM
  • Firstpage
    418
  • Lastpage
    418
  • Abstract
    SHORT time transients such as lightning waves and switching surges cause very high o ver-voltages in transformers due to high amplitudes of these voltages allowed by transmission line insulation and the non-uniform distribution of such voltages throughout the winding and internal resonance. The internal stresses can be reduced by limiting the amplitude of the impulse waves (gaps and lightning arresters), by changing their shape (wave modifiers), by making voltage distribution uniform throughout the winding irrespective of the shape of the wave (electrostatic shielding of the windings) or by a combination of these means. Coil, turn, and major insulation (except at line end) transient voltages are reduced far more by making the voltage distribution uniform throughout the winding then by reducing the amplitude of the applied wave by any means available at present.