Title
Removing Insertion Impedance Effects From Transformer Admittance Measurements
Author
Gustavsen, Bjørn
Author_Institution
SINTEF Energy Res., Trondheim, Norway
Volume
27
Issue
2
fYear
2012
fDate
4/1/2012 12:00:00 AM
Firstpage
1027
Lastpage
1029
Abstract
Frequency-domain measurements can be used for obtaining a wideband model of a power transformer via its terminal admittance matrix. This paper shows that the current sensor used in the measurements can significantly affect the elements of the obtained admittance matrix by its insertion impedance. The insertion impedance influences diagonal and off-diagonal elements, often leading to asymmetries in the matrix for transformers having a high-voltage ratio. Formulae are developed which are capable of removing these effects. The procedure is demonstrated for a distribution transformer.
Keywords
electric admittance measurement; power transformers; current sensor; distribution transformer; frequency-domain measurements; high-voltage ratio; insertion impedance effects; off-diagonal elements; terminal admittance matrix; transformer admittance measurements; Admittance; Admittance measurement; Current measurement; Impedance; Impedance measurement; Power transformers; Voltage measurement; Admittance matrix; asymmetry; frequency domain; measurements; transformer; wideband;