    Removing Insertion Impedance Effects From Transformer Admittance Measurements

  • Author

    Gustavsen, Bjørn

  • Author_Institution
    SINTEF Energy Res., Trondheim, Norway
  • Volume
    27
  • Issue
    2
  • fYear
    2012
  • fDate
    4/1/2012 12:00:00 AM
  • Firstpage
    1027
  • Lastpage
    1029
  • Abstract
    Frequency-domain measurements can be used for obtaining a wideband model of a power transformer via its terminal admittance matrix. This paper shows that the current sensor used in the measurements can significantly affect the elements of the obtained admittance matrix by its insertion impedance. The insertion impedance influences diagonal and off-diagonal elements, often leading to asymmetries in the matrix for transformers having a high-voltage ratio. Formulae are developed which are capable of removing these effects. The procedure is demonstrated for a distribution transformer.
  • Keywords
    electric admittance measurement; power transformers; current sensor; distribution transformer; frequency-domain measurements; high-voltage ratio; insertion impedance effects; off-diagonal elements; terminal admittance matrix; transformer admittance measurements; Admittance; Admittance measurement; Current measurement; Impedance; Impedance measurement; Power transformers; Voltage measurement; Admittance matrix; asymmetry; frequency domain; measurements; transformer; wideband;