DocumentCode :
1416559
Title :
The Optimization of Entering Route for Live Working on 750 kV Transmission Towers by Space Electric-Field Analysis
Author :
Zhuang, Chijie ; Zeng, Rong ; Zhang, Bo ; Zhu, Puxuan ; Wang, Ling ; He, Jinliang
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume :
25
Issue :
2
fYear :
2010
fDate :
4/1/2010 12:00:00 AM
Firstpage :
987
Lastpage :
994
Abstract :
Live working is important for the continuity of electricity supply in power system. Experiment results of 50% switching impulse sparkover voltages (U50) for different live working entering routes on a real tower are presented. The potential and electric-field distribution around the 750 kV straight tower window with a line worker inside, was analyzed via an approach combing charge simulation method and indirect boundary element method. The comparison demonstrates the close relationship between electric-field distribution and U50. The sparkover voltage and the maximum electric-field strength change synchronously for a specific structure. Generally speaking, the higher the electric filed strength is, the lower the sparkover voltage will be. Thus, the experiment procedure for deciding the best entering route can be simplified according to the electric-field distribution calculation.
Keywords :
boundary-elements methods; electric fields; poles and towers; sparks; boundary element method; electric-field distribution calculation; entering route optimization; maximum electric-field strength; power system electricity supply; space electric-field analysis; transmission towers; voltage 750 kV; Charge simulation method; electric-field distribution; indirect boundary element method; live working; transmission tower;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2038918
Filename :
5411954
Link To Document :
بازگشت