DocumentCode
1416559
Title
The Optimization of Entering Route for Live Working on 750 kV Transmission Towers by Space Electric-Field Analysis
Author
Zhuang, Chijie ; Zeng, Rong ; Zhang, Bo ; Zhu, Puxuan ; Wang, Ling ; He, Jinliang
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume
25
Issue
2
fYear
2010
fDate
4/1/2010 12:00:00 AM
Firstpage
987
Lastpage
994
Abstract
Live working is important for the continuity of electricity supply in power system. Experiment results of 50% switching impulse sparkover voltages (U50) for different live working entering routes on a real tower are presented. The potential and electric-field distribution around the 750 kV straight tower window with a line worker inside, was analyzed via an approach combing charge simulation method and indirect boundary element method. The comparison demonstrates the close relationship between electric-field distribution and U50. The sparkover voltage and the maximum electric-field strength change synchronously for a specific structure. Generally speaking, the higher the electric filed strength is, the lower the sparkover voltage will be. Thus, the experiment procedure for deciding the best entering route can be simplified according to the electric-field distribution calculation.
Keywords
boundary-elements methods; electric fields; poles and towers; sparks; boundary element method; electric-field distribution calculation; entering route optimization; maximum electric-field strength; power system electricity supply; space electric-field analysis; transmission towers; voltage 750 kV; Charge simulation method; electric-field distribution; indirect boundary element method; live working; transmission tower;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2038918
Filename
5411954