    The electrostatic unbalance of transmission lines and its effect on the application of Petersen coils

  • Author

    Lyon, John Alexander Melvin

  • Author_Institution
    Johns Hopkins University, Baltimore, Md.; E. M. Gilbert Engineering Corporation and of the Utility Management Corporation
  • Volume
    58
  • Issue
    3
  • fYear
    1939
  • fDate
    3/1/1939 12:00:00 AM
  • Firstpage
    107
  • Lastpage
    112
  • Abstract
    RECENTLY three Petersen coils were installed on the 66-kv transmission system of the Metropolitan Edison Company of Pennsylvania. These Petersen coils provide service protection to approximately 320 miles of overhead transmission lines against outages and voltage dips which would otherwise result when single phase-to-ground flashovers occur on the system. Much of the 66-kv transmission system consists of two-circuit lines with vertical configurations of the line conductors with no transpositions prior to the Petersen-coil installation.