DocumentCode :
1421099
Title :
Five years´ experience with ultrahigh-speed reclosing of high-voltage transmission lines
Author :
Sporn, Philip ; Muller, C. A.
Author_Institution :
American Gas and Electric Service Corporation, New York, N. Y.
Volume :
60
Issue :
5
fYear :
1941
fDate :
5/1/1941 12:00:00 AM
Firstpage :
241
Lastpage :
245
Abstract :
The data covering five years´ operating experience with 33 ultrahigh-speed reclosing breaker installations mainly on a large interconnected and integrated high-tension system are presented and analyzed, and conclusions based on this experience are drawn. Out of 71 cases of flashover cited, 65 reclosures were successful and 6 cases of reclosure resulted in restrikes, a record of 91.5 per cent successful reclosures. The conclusions drawn are that not only is actual performance better than appeared possible when the development was first made but that further improvements are possible by further reducing breaker time.
Keywords :
Circuit faults; Flashover; Lightning; Poles and towers; Power transmission lines; Relays;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1941.6432118
Filename :
6432118
Link To Document :