DocumentCode
1421106
Title
New approach to distance relays with quadrilateral polar characteristic for e.h.v.-line protection
Author
Kumar, N. M Anil
Author_Institution
Indian Institute of Science, Department of Electrical Engineering, Bangalore, India
Volume
117
Issue
10
fYear
1970
fDate
10/1/1970 12:00:00 AM
Firstpage
1986
Lastpage
1992
Abstract
A new technique is presented using principles of multisignal relaying for the synthesis of a universal-type quadrilateral polar characteristic. The modus operandi consists in the determination of the phase sequence of a set of voltage phasors and the provision of a trip signal for one sequence while blocking for the other. Two versions, one using ferrite-core logic and another using transistor logic, are described in detail. The former version has the merit of simplicity and has the added advantage of not requiring any d.c. supply. The unit is flexible, as it permits independent control of the characteristic along the resistance and reactance axis through suitable adjustments of replica impedance angles. The maximum operating time is about 20ms for all switching angles, and with faults within 95% of the protected section. The maximum transient overreach is about 8%.
Keywords
power transmission; relay protection;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1970.0350