DocumentCode
1422275
Title
Development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS
Author
Hasegawa, T. ; Yamaji, K. ; Hatano, M. ; Endo, F. ; Rokunohe, T. ; Yamagiwa, T.
Author_Institution
Kansai Electr. Power Co. Inc., Osaka, Japan
Volume
12
Issue
1
fYear
1997
fDate
1/1/1997 12:00:00 AM
Firstpage
194
Lastpage
202
Abstract
The paper describes the development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS (gas insulated switchgear). Considering problems of metallic particles and charge accumulation on spacers, the developed insulation structure of GIS consisted of three regions, i.e. the spacer, particle scavenging and nonlevitating regions. Particles could be efficiently scavenged, and the developed GIS withstood all insulation specifications with sufficient margins under the clean and particle-contaminated condition. Now, a long-term site test for one year of the 500 kV DC GIS has been continued since October in 1995
Keywords
HVDC power transmission; circuit breakers; gas insulated switchgear; insulation testing; reliability; 500 kV; HVDC gas insulated switchgear; charge accumulation; insulation reliability enhancement; insulation structure; metallic particles; nonlevitating regions; particle scavenging; particle-contaminated condition; Conductors; Electrodes; Geographic Information Systems; Insulation; Partial discharges; Samarium; Shape; Surface charging; Testing; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.568241
Filename
568241
Link To Document