• DocumentCode
    1422275
  • Title

    Development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS

  • Author

    Hasegawa, T. ; Yamaji, K. ; Hatano, M. ; Endo, F. ; Rokunohe, T. ; Yamagiwa, T.

  • Author_Institution
    Kansai Electr. Power Co. Inc., Osaka, Japan
  • Volume
    12
  • Issue
    1
  • fYear
    1997
  • fDate
    1/1/1997 12:00:00 AM
  • Firstpage
    194
  • Lastpage
    202
  • Abstract
    The paper describes the development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS (gas insulated switchgear). Considering problems of metallic particles and charge accumulation on spacers, the developed insulation structure of GIS consisted of three regions, i.e. the spacer, particle scavenging and nonlevitating regions. Particles could be efficiently scavenged, and the developed GIS withstood all insulation specifications with sufficient margins under the clean and particle-contaminated condition. Now, a long-term site test for one year of the 500 kV DC GIS has been continued since October in 1995
  • Keywords
    HVDC power transmission; circuit breakers; gas insulated switchgear; insulation testing; reliability; 500 kV; HVDC gas insulated switchgear; charge accumulation; insulation reliability enhancement; insulation structure; metallic particles; nonlevitating regions; particle scavenging; particle-contaminated condition; Conductors; Electrodes; Geographic Information Systems; Insulation; Partial discharges; Samarium; Shape; Surface charging; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.568241
  • Filename
    568241