DocumentCode :
1422440
Title :
An improved transformer top oil temperature model for use in an on-line monitoring and diagnostic system
Author :
Lesieutre, B.C. ; Hagman, W.H. ; Kirtley, J.L., Jr.
Author_Institution :
Lab. for Electromagn. & Electron. Syst., MIT, Cambridge, MA, USA
Volume :
12
Issue :
1
fYear :
1997
fDate :
1/1/1997 12:00:00 AM
Firstpage :
249
Lastpage :
256
Abstract :
In this paper, the authors examine dynamic models of power transformer top oil temperature for use in an online monitoring and diagnostic system. Data taken from large transformers in the field indicate that the IEEE model of top oil temperature rise over ambient temperature does not adequately account for daily variations in ambient temperature. The authors propose a modification that accurately predicts top oil temperature and can be implemented in an online system. This model is verified using data from a large power transformer in service
Keywords :
power transformer insulation; power transformers; thermal analysis; transformer oil; IEEE model; online diagnosis system; online monitoring system; power transformer top oil temperature; thermal modelling; top oil temperature rise; Condition monitoring; Electromagnetic modeling; Heat transfer; Laboratories; Oil insulation; Petroleum; Power measurement; Predictive models; Temperature dependence; Thermal loading;