DocumentCode :
1422456
Title :
A shunt active power filter applied to high voltage distribution lines
Author :
Häfner, J. ; Aredes, M. ; Heumann, K.
Author_Institution :
Inst. fur Allgemeine Elektrotech., Tech. Univ. Berlin, Germany
Volume :
12
Issue :
1
fYear :
1997
fDate :
1/1/1997 12:00:00 AM
Firstpage :
266
Lastpage :
272
Abstract :
The high requirement of rated power of an active power filter leads to high costs and limits the range of operation especially for high voltage applications. To overcome these problems, a combined system of a passive filter, using only one LC filter tuned to the lowest typical line current harmonic, and a shunt active power filter, sharing the filter capacitor to be decoupled from the fundamental line voltage, is proposed. These features strongly decrease the rated power of the active filter which is controlled only to suppress the harmonics of higher order and to eliminate resonance effects between the line impedance and the passive filter
Keywords :
active filters; distribution networks; harmonic distortion; power capacitors; power filters; power system harmonics; thyristor convertors; HV distribution lines; capacitor banks; filter capacitor; fundamental line voltage; higher harmonics suppression; line current harmonic; rated power requirement; resonance effects; shunt active power filter; thyristor controlled reactor; thyristor power convertors; Active filters; Capacitors; Impedance; Passive filters; Power harmonic filters; Power system harmonics; Resonance; Shunt (electrical); Thyristors; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.568249