Title :
Transactions section: Preprint of corresponding pages from the current annual transactions volume: Bus protection independent of current transformer characteristics
Author_Institution :
Buffalo, Niagara and Eastern Power Corporation, Buffalo, N. Y.
Abstract :
The paper describes the installation and operating results of a bus protective scheme. which uses a combination of high-speed directional ground relays on all sources of fault current and high-speed plunger type blocking relays on all outgoing circuits. The scheme described is independent of the ratios and characteristics of the current transformers.
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1941.6432368