Abstract :
Harmonic resonance has been observed, measured and modeled on parallel 500-kV lines that are about one wavelength at 2100 Hz, the 35th harmonic. A seemingly small harmonic injection at one location on the system causes significant problems some distance away such as telephone interference
Keywords :
electromagnetic interference; power system harmonics; power system measurement; power transmission lines; resonance; telephone interference; 2100 Hz; 35th harmonic; 500 kV; harmonic injection; harmonic resonance measurement; harmonic resonance modelling; parallel high voltage transmission lines; telephone interference; Capacitors; Interference; Lakes; Power transmission lines; Resonance; Substations; Telephony; Testing; Transmission lines; Voltage;
Journal_Title :