• DocumentCode
    1422776
  • Title

    A nondifferential protection scheme for generator stator windings

  • Author

    Bo, Z.Q. ; Chen, Z. ; Redfern, M.A. ; Potts, S. ; McCormick, M. ; Weller, G.

  • Author_Institution
    ALSTOM T&D Protection & Control Ltd., Stafford, UK
  • Volume
    21
  • Issue
    1
  • fYear
    2001
  • fDate
    1/1/2001 12:00:00 AM
  • Firstpage
    49
  • Lastpage
    51
  • Abstract
    This letter presents a new technique for generator protection. The fault-generated transient current signals are detected using a multichannel transient detection unit, then the spectral energies at different frequency bands are extracted and compared to discriminate between internal and external faults. Simulation results show that the scheme demonstrates good sensitivity to low-level and interturn faults
  • Keywords
    electric generators; electrical faults; machine protection; stators; transient analysis; external faults; fault-generated transient current signals; frequency bands; generator stator windings; internal faults; interturn faults; low-level faults; multichannel transient detection unit; nondifferential protection scheme; spectral energies; Circuit faults; Current transformers; Electrical fault detection; Fault detection; Frequency; Impedance; Power system transients; Protection; Protective relaying; Stator windings;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/39.893341
  • Filename
    893341