DocumentCode
1423953
Title
Direct method for calculation of AC side harmonics and interharmonics in an HVDC system
Author
Hu, L. ; Ran, L.
Author_Institution
Business Innovation Centre, UK
Volume
147
Issue
6
fYear
2000
fDate
11/1/2000 12:00:00 AM
Firstpage
329
Lastpage
335
Abstract
AC side current harmonics in an HVDC system are shown to be dependent on the commutation overlap and the DC side ripple. Interharmonics exist when the AC networks operate at different frequencies. An analytical method is proposed to represent such effects in the AC side harmonic calculation. The algorithm does not require iteration between the AC and DC sides. The result obtained using the analytical method is verified using time domain simulation
Keywords
HVDC power transmission; commutation; harmonic analysis; power system harmonics; power system interconnection; time-domain analysis; AC side harmonics; DC side ripple; HVDC system; commutation overlap; interharmonics; time domain simulation;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:20000668
Filename
894393
Link To Document