• DocumentCode
    1424245
  • Title

    Online Tracking of Thévenin Equivalent Parameters Using PMU Measurements

  • Author

    Abdelkader, Sobhy M. ; Morrow, D. John

  • Author_Institution
    Electr. Eng. Dept., Mansoura Univ., Mansoura, Egypt
  • Volume
    27
  • Issue
    2
  • fYear
    2012
  • fDate
    5/1/2012 12:00:00 AM
  • Firstpage
    975
  • Lastpage
    983
  • Abstract
    This paper presents a new method for tracking Thévenin equivalent parameters for a power system at a node using local phasor measurement unit (PMU) measurements. Three consecutive phasor measurements for voltage and current, recorded at one location, are used. The phase drifts caused by the measurement slip frequency are first determined and phase angles of the measured phasors are corrected so that the corrected phasors are synchronized to the same reference. The synchronized phasors are then used to determine the equivalent Thévenin parameters of the system.
  • Keywords
    phasor measurement; PMU measurements; Thevenin equivalent parameters; local phasor measurement unit measurements; measurement slip frequency; online tracking; phase drifts; synchronized phasors; Current measurement; Frequency measurement; Phase measurement; Phasor measurement units; Power system stability; Synchronization; Voltage measurement; Phasor measurement; Thévenin equivalent; power system;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2011.2178868
  • Filename
    6132444