DocumentCode
1424245
Title
Online Tracking of Thévenin Equivalent Parameters Using PMU Measurements
Author
Abdelkader, Sobhy M. ; Morrow, D. John
Author_Institution
Electr. Eng. Dept., Mansoura Univ., Mansoura, Egypt
Volume
27
Issue
2
fYear
2012
fDate
5/1/2012 12:00:00 AM
Firstpage
975
Lastpage
983
Abstract
This paper presents a new method for tracking Thévenin equivalent parameters for a power system at a node using local phasor measurement unit (PMU) measurements. Three consecutive phasor measurements for voltage and current, recorded at one location, are used. The phase drifts caused by the measurement slip frequency are first determined and phase angles of the measured phasors are corrected so that the corrected phasors are synchronized to the same reference. The synchronized phasors are then used to determine the equivalent Thévenin parameters of the system.
Keywords
phasor measurement; PMU measurements; Thevenin equivalent parameters; local phasor measurement unit measurements; measurement slip frequency; online tracking; phase drifts; synchronized phasors; Current measurement; Frequency measurement; Phase measurement; Phasor measurement units; Power system stability; Synchronization; Voltage measurement; Phasor measurement; Thévenin equivalent; power system;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2011.2178868
Filename