DocumentCode
1424353
Title
The Peak Value of Lightning-Induced Voltages in Overhead Lines Considering the Ground Resistivity and Typical Return Stroke Parameters
Author
Paulino, José Osvaldo S ; Barbosa, Célio Fonseca ; Lopes, Ivan J S ; Boaventura, Wallace Do Couto
Author_Institution
Dept. of Electr. Eng., Univ. Fed. de Minas Gerais, Belo Horizonte, Brazil
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
920
Lastpage
927
Abstract
This paper presents an approximate formula for the peak value of lightning-induced voltages in an overhead line, considering the ground resistivity and a trapezoidal lightning return stroke current waveform with typical parameters 3.8-μ s front time and 120-m/μ s velocity. It presents an improvement in a formula previously proposed by the authors. The formula is used with a probabilistic approach, and the results are compared with theoretical and experimental results available in the literature. The results show that the proposed formula, although very simple, is in good agreement with results obtained using complete formulations and experimental data.
Keywords
electric resistance; lightning; power distribution lines; power overhead lines; probability; ground resistivity; lightning-induced voltages; overhead distribution line; probabilistic approach; return stroke parameters; trapezoidal lightning; Induced voltage; lightning; overhead distribution line; soil conductivity;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2095887
Filename
5686895
Link To Document