DocumentCode :
1425037
Title :
Pilot-wire protection of transmission lines
Author :
Neher, J. H.
Author_Institution :
Philadelphia Electric Company, Philadelphia, Pa.
Volume :
79
Issue :
8
fYear :
1960
Firstpage :
637
Lastpage :
637
Abstract :
THE PRESENT pilot-wire protective systems for transmission lines employing leased pilot-wire circuits are an outgrowth of conventional differential protective systems for other types of electric apparatus. Thus, these line-protective systems are characterized by the fact that the pilot wires are part of the differential connection between the current transformers at the line ends. The pilot wire has distributed shunt capacitance as well as series resistance, with the result that when these parameters reach sufficient magnitude, attenuation and undesirable phase shifts occur in the pilot-wire circuit. Thus, the system may be prevented from functioning correctly under certain operating conditions.
Keywords :
Attenuation; Coils; Impedance; Power transmission lines; Relays; Wires;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1960.6432760
Filename :
6432760
Link To Document :
بازگشت