DocumentCode :
1426105
Title :
Distance protection and fault location utilizing only phase current phasors
Author :
Djuric, M.B. ; Radojevic, Z.M. ; Terzija, V.V.
Author_Institution :
Fac. of Electr. Eng., Belgrade Univ., Serbia
Volume :
13
Issue :
4
fYear :
1998
fDate :
10/1/1998 12:00:00 AM
Firstpage :
1020
Lastpage :
1026
Abstract :
Two numerical algorithms for fault location and distance protection which use data from one end of a transmission line are presented. Both algorithms require only current signals as input data. Voltage signals are unnecessary for determining the unknown distance to the fault. The solution for the most frequent phase to ground fault is presented. The algorithms are relatively simple and easy to be implemented in the on-line application. The algorithms allow for accurate calculation of the fault location irrespective of the fault resistance and load. To illustrate the features of the new algorithms, steady-state and dynamic tests are presented
Keywords :
fault location; microcomputer applications; power engineering computing; power system protection; relay protection; computer relaying; current signals; distance protection; dynamic tests; fault location; numerical algorithms; on-line application; phase current phasors; phase to ground fault; steady-state tests; Circuit faults; Distributed parameter circuits; Fault location; Impedance; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Substation protection; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.714437
Filename :
714437
Link To Document :
بازگشت