• DocumentCode
    1426128
  • Title

    Wide-area current differential backup protection employing broadband communications and time transfer systems

  • Author

    Serizawa, U. ; Myoujin, M. ; Kitamura, K. ; Sugaya, N. ; Hori, M. ; Takeuchi, A. ; Shuto, I. ; Inukai, Motoharu

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    13
  • Issue
    4
  • fYear
    1998
  • fDate
    10/1/1998 12:00:00 AM
  • Firstpage
    1046
  • Lastpage
    1052
  • Abstract
    As power systems grow larger, it is becoming difficult to achieve reach and time coordination in backup protection when using distance relays. To cope with those problems, current differential backup protection for a busbar and transmission circuits connected to that busbar on an inter-station or wide-area basis is proposed. The proposed system can operate better than conventional systems with respect to operation time, section selectivity, etc. A system configuration is also proposed to utilize ATM transmission networks and time synchronous systems which make the construction and operation of the proposed wide-area protection system easy and flexible
  • Keywords
    asynchronous transfer mode; broadband networks; power system control; power system protection; power system relaying; relay protection; telecontrol; ATM transmission networks; broadband communications; busbar; current differential backup protection; operation time; section selectivity; time coordination; time synchronous systems; time transfer systems; transmission circuits; wide-area power system protection; Asynchronous transfer mode; Broadband communication; Circuits; Global Positioning System; Load flow; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Substation protection;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.714445
  • Filename
    714445