• DocumentCode
    1426200
  • Title

    Grounding resistance measurement using fall-of-potential method with potential probe located in opposite direction to the current probe

  • Author

    Wang, Cheng-gang ; Takasima, Takeshi ; Sakuta, Tadahiro ; Tsubota, Yoshimasa

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Kanazawa Univ., Japan
  • Volume
    13
  • Issue
    4
  • fYear
    1998
  • fDate
    10/1/1998 12:00:00 AM
  • Firstpage
    1128
  • Lastpage
    1135
  • Abstract
    This paper presents errors in grounding resistance measurement using the fall-of-potential method with the potential probe located in the opposite direction to the current probe. Errors are obtained with computer simulation. Such ground electrodes as a counterpoise, a grid, a rod and a combination of them are considered here. The soil is supposed to be extended to two-layer structure. Numerical results are computed by the current source simulation method and the method of images
  • Keywords
    earth electrodes; electric resistance measurement; measurement errors; measurement theory; power system measurement; power system protection; probes; computer simulation; current probe; current source simulation method; fall-of-potential method; ground electrodes; grounding resistance measurement errors; images method; potential probe; two-layer soil structure; Computer errors; Conductors; Current measurement; Electrical resistance measurement; Electrodes; Grounding; Power engineering computing; Probes; Soil; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.714472
  • Filename
    714472