DocumentCode :
1426200
Title :
Grounding resistance measurement using fall-of-potential method with potential probe located in opposite direction to the current probe
Author :
Wang, Cheng-gang ; Takasima, Takeshi ; Sakuta, Tadahiro ; Tsubota, Yoshimasa
Author_Institution :
Dept. of Electr. & Comput. Eng., Kanazawa Univ., Japan
Volume :
13
Issue :
4
fYear :
1998
fDate :
10/1/1998 12:00:00 AM
Firstpage :
1128
Lastpage :
1135
Abstract :
This paper presents errors in grounding resistance measurement using the fall-of-potential method with the potential probe located in the opposite direction to the current probe. Errors are obtained with computer simulation. Such ground electrodes as a counterpoise, a grid, a rod and a combination of them are considered here. The soil is supposed to be extended to two-layer structure. Numerical results are computed by the current source simulation method and the method of images
Keywords :
earth electrodes; electric resistance measurement; measurement errors; measurement theory; power system measurement; power system protection; probes; computer simulation; current probe; current source simulation method; fall-of-potential method; ground electrodes; grounding resistance measurement errors; images method; potential probe; two-layer soil structure; Computer errors; Conductors; Current measurement; Electrical resistance measurement; Electrodes; Grounding; Power engineering computing; Probes; Soil; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.714472
Filename :
714472
Link To Document :
بازگشت