DocumentCode
1427063
Title
Evaluation and testing of a single terminal step distance scheme for use on a six phase transmission system
Author
Oppel, L.J. ; Krizauskas, E. ; Austenfeld, R.H.
Author_Institution
Power Technol. Inc., Schenectady, NY, USA
Volume
13
Issue
4
fYear
1998
fDate
10/1/1998 12:00:00 AM
Firstpage
1527
Lastpage
1529
Abstract
This paper describes a single terminal step distance scheme using commercially available relays for use on a six-phase transmission line, and gives the results of its performance for simulated faults on a six-phase transmission system with all phases in service, and with one, two, or three phases out of service. This paper also gives an overview and evaluation of the testing of the scheme via low level analog test sets. This project was sponsored by Electric Power Research Institute (EPRI), the Department of Energy (DOE), Empire State Electric Energy Research Corporation (ESEERCO), New York State Energy Office (SEO), New York State Energy Research and Development Authority (NYSERDA) and New York State Electric and Gas Corporation (NYSEG)
Keywords
electrical faults; power system protection; relay protection; testing; transmission networks; Department of Energy; EPRI; Electric Power Research Institute; Empire State Electric Energy Research Corporation; New York State Electric and Gas Corporation; New York State Energy Office; New York State Energy Research and Development Authority; faults simulation; low level analog test sets; one phase out of service; single terminal step distance scheme; six phase transmission system; testing; three phases out of service; two phases out of service; Circuit faults; Load flow; Logic; Monitoring; Power transmission lines; Protection; Protective relaying; Relays; Testing; Transformers;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.714851