DocumentCode
1427068
Title
External thermal resistance of two buried cables. Restricted application of superposition
Author
Goldenberg, H.
Author_Institution
Electrical Research Association, Leatherhead, UK
Volume
116
Issue
5
fYear
1969
fDate
5/1/1969 12:00:00 AM
Firstpage
822
Lastpage
826
Abstract
New formulas are derived for the external thermal resistance of one of two equally loaded identical cables laid direct in the ground at the same depth. The formulas are based on a restricted application of the principle of superposition, and remain valid when the cables are close or touching. Two assumptions made are that the depth of the buried cables is much greater than the cable radius, and that the cable surfaces are isothermal at a common temperature. The former assumption is justified as the cable depth is generally equal to at least ten times the cable radius. The latter assumption is recognised to be an approximation, but the present approach may prove to be more acceptable than alternative techniques. Comparison is made with previously published formulas.
Keywords
power cables;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1969.0156
Filename
5250158
Link To Document