DocumentCode
1429126
Title
Distance relay performance as affected by capacitor voltage transformers
Author
Hughes, M.A.
Author_Institution
General Electric Co., St. Leonards Works, Stafford, UK
Volume
121
Issue
12
fYear
1974
fDate
12/1/1974 12:00:00 AM
Firstpage
1557
Lastpage
1566
Abstract
A 3-phase capacitor-voltage-transformer simulation is described which, when used in conjunction with a conventional artificial transmission line, allows complete relaying schemes to be tested. The accuracy of the simulation is confirmed by comparison of its response with that of a full-scale capacitor voltage transformer. Conjunctive distance-relay/capacitor-voltage-transformer tests are reported showing that transient errors degrade relay performance in speed and stability. Various methods for providing a more faithful voltage signal to supply the relay circuits are discussed.
Keywords
potential transformers; relay protection; simulation; capacitor voltage transformers; distance relay performance; simulation; tests; transient errors;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1974.0321
Filename
5250882
Link To Document