Abstract :
A 3-phase capacitor-voltage-transformer simulation is described which, when used in conjunction with a conventional artificial transmission line, allows complete relaying schemes to be tested. The accuracy of the simulation is confirmed by comparison of its response with that of a full-scale capacitor voltage transformer. Conjunctive distance-relay/capacitor-voltage-transformer tests are reported showing that transient errors degrade relay performance in speed and stability. Various methods for providing a more faithful voltage signal to supply the relay circuits are discussed.
Keywords :
potential transformers; relay protection; simulation; capacitor voltage transformers; distance relay performance; simulation; tests; transient errors;