Behaviour of h.v. d.c. links under unbalanced-a.c.-fault conditions
Author
Giesner, D.B. ; Arrillaga, J.
Author_Institution
Monash University, Electrical Engineering Department, Melbourne, Australia
Volume
119
Issue
2
fYear
1972
fDate
2/1/1972 12:00:00 AM
Firstpage
209
Lastpage
215
Abstract
A theoretical analysis is made of the production of triplen-harmonic currents by a convertor bridge using symmetrical firing control when supplied with unbalanced 3-phase voltages. It is shown that these harmonic currents can pass into the a.c. system regardless of the transformer connections. Results are obtained from a digital-computer program for the dynamic behaviour of an a.c.-d.c. interconnected system during single- and 2-phase faults, and particular importance is given to their effect on a weak a.c. system.
Keywords
DC power transmission; fault currents; harmonic analysis; convertor bridge; dynamic behaviour; faults; symmetrical firing control; theoretical analysis; triplen harmonic currents;