DocumentCode :
1429881
Title :
Analysis of the effect of humidity on d.c. corona power losses
Author :
Khalifa, M. ; El-Debeiky, S.
Author_Institution :
University of Cairo, Electrical Department, Cairo, United Arab Republic
Volume :
118
Issue :
5
fYear :
1971
fDate :
5/1/1971 12:00:00 AM
Firstpage :
714
Lastpage :
718
Abstract :
A method is presented for calculating the effects of atmospheric humidity on d. c. corona losses. The experimentally observed increase of the losses with humidity is explained. At conductor voltages near the inception level, an approximately cubic relationship is found between corona losses and relative humidity. The relationship is less sensitive at higher voltages.
Keywords :
corona; losses; transmission networks; DC; HV; atmospheric humidity effects; conductor voltage; corona losses; cubic loss relationship; discharges; inception level; transmission networks;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1971.0131
Filename :
5251029
Link To Document :
بازگشت