DocumentCode
1430426
Title
Power Transformer Differential Protection Based on Clarke´s Transform and Fuzzy Systems
Author
Barbosa, Daniel ; Netto, Ulisses Chemin ; Coury, Denis V. ; Oleskovicz, Mário
Author_Institution
Salvador Univ., Salvador, Brazil
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
1212
Lastpage
1220
Abstract
The power transformer is a piece of electrical equipment that needs continuous monitoring and fast protection since it is very expensive and an essential element for a power system to perform effectively. The most common protection technique used is the percentage differential logic, which provides discrimination between an internal fault and different operating conditions. Unfortunately, there are some operating conditions of power transformers that can affect the protection behavior and the power system stability. This paper proposes the development of a new algorithm to improve the differential protection performance by using fuzzy logic and Clarke´s transform. An electrical power system was modeled using Alternative Transients Program (ATP) software to obtain the operational conditions and fault situations needed to test the algorithm developed. The results were compared to a commercial relay for validation, showing the advantages of the new method.
Keywords
fuzzy logic; power engineering computing; power system stability; power transformer protection; Clarke transform; alternative transients program software; differential protection performance; electrical equipment; electrical power system; fuzzy logic; power system stability; power transformer differential protection; Alternate Transients Program (ATP); Clarke´s transform; differential protection; fuzzy system; power transformer;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2097281
Filename
5692875
Link To Document