• DocumentCode
    1435811
  • Title

    Some aspects of generator backup protection in relation to synchronous-machine performance during h.v.-system faults

  • Author

    Cook, V. ; Rushton, J.

  • Author_Institution
    University College, Cardiff, UK
  • Volume
    119
  • Issue
    7
  • fYear
    1972
  • fDate
    7/1/1972 12:00:00 AM
  • Firstpage
    865
  • Lastpage
    870
  • Abstract
    The fault performance of large generator units is considered in relation to the selection of generator-backup-protection settings, and a method of determining protection performance is presented, based on a simplified analysis of generator fault currents and neglecting rotor-angle swings. The validity of this approach is demonstrated and the method is used to determine the fault performance of negative-phase-sequence current and overcurrent protection. Alternative methods of overcurrent protection are examined which appear to provide improved backup protection for internal and external faults.
  • Keywords
    electric generators; overcurrent protection; power system protection; synchronous machines; fault currents; generator backup protection; generator fault currents; negative phase sequence current protection; overcurrent protection; synchronous machine performance during HV system faults;