Measurement Uncertainties of Impulse Parameters Due to Nonideal Step Responses of High-Voltage Dividers
Author :
Li, Yi ; Ediriweera, Miyuru K.
Author_Institution :
Nat. Meas. Inst., Lindfield, NSW, Australia
Volume :
60
Issue :
7
fYear :
2011
fDate :
7/1/2011 12:00:00 AM
Firstpage :
2217
Lastpage :
2222
Abstract :
Using the new definitions and analysis specified in the 2010 version of the IEC standards to calculate impulse parameters, this paper investigates the measurement errors and uncertainties of high-voltage impulse dividers due to their nonideal step response using the convolution method. Measured step responses of three different dividers and a range of practical impulse waveforms were used in the calculations. The obtained results indicate, for the first time, that the uncertainty contribution of a nonideal step response can be estimated with sufficient accuracy for the purpose of measuring practical impulse waveforms.
Keywords :
IEC standards; measurement errors; measurement uncertainty; step response; voltage dividers; voltage measurement; waveform analysis; IEC standard; convolution method; high-voltage impulse divider; impulse parameter calculation; impulse waveform measurement; measurement errors; measurement uncertainty; nonideal step response; Calibration; Convolution; Lightning; Measurement uncertainty; Oscillators; Testing; Uncertainty; Convolution; high-voltage techniques; impulse testing; lightning; measurement uncertainty;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/TIM.2010.2103411
Filename :
5703128
Link To Document :
بازگشت