DocumentCode :
1437828
Title :
Voltage stability and thermal limit: constraints on the maximum loading of electrical energy distribution feeders
Author :
Prada, R.B. ; Souza, L.J.
Author_Institution :
Dept. of Electr. Eng., Catholic Univ. of Rio de Janeiro, Brazil
Volume :
145
Issue :
5
fYear :
1998
fDate :
9/1/1998 12:00:00 AM
Firstpage :
573
Lastpage :
577
Abstract :
The loading condition of distribution systems is assessed with respect to voltage stability as well as to thermal limit. Real networks of a distribution utility of Brazil are used in the tests performed. Results show that the maximum loading may be limited by voltage stability rather than by thermal limit. The paper shows the necessity of considering voltage stability as a new constraint on the operational loading of electrical energy distribution feeders, including the connection of new consumers. The voltage stability constraint should be considered in studies concerning distribution systems expansion. The new planning constraint may avoid the building of new lines and transformers which could never be fully used in systems already stressed by voltage stability
Keywords :
distribution networks; power system stability; thermal analysis; Brazil; distribution systems expansion; distribution utility; electrical energy distribution feeders; loading condition; maximum loading; new consumers connection; operational loading; planning constraint; thermal limit; voltage stability;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19982186