Title :
Lightning protection of wood-pole lines
Author :
Sels, H. K. ; Gothberg, A. W.
Author_Institution :
Public Service Electric and Gas Company, Newark, N. J.
fDate :
6/1/1940 12:00:00 AM
Abstract :
The reliability of wood-pole transmission lines during the lightning season has long been a problem with operating companies. To meet the ever increasing service demands approximately 60 miles of line were reconstructed using the inherent insulation of a wood-pole line with lightning protector tubes on one of three conductors. Two years´ experience with this type of construction has shown better than a 90 per cent reduction in lightning outages.
Keywords :
Circuit faults; Conductors; Electron tubes; Interrupters; Lightning protection; Wires;
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1940.6434961