DocumentCode
1438296
Title
Real-time monitoring of power systems using fast-decoupled load flow
Author
Tripathy, S.C. ; Rao, N.D. ; Kumar, Arun
Author_Institution
University of Calgary, Electrical Engineering Department, Calgary, Canada
Volume
124
Issue
7
fYear
1977
fDate
7/1/1977 12:00:00 AM
Firstpage
602
Lastpage
606
Abstract
The paper presents the implementation of the fast-decoupled load-flow technique for real-time monitoring of power systems in the presence of metering inaccuracies and data-acquisition failures. The real-time load-flow solution with mode injections and redundant line flows, using the fast-decoupled load flow, is much faster and requires less computer storage than that using conventional Newton-Raphson method, but still provides the same accuracy. Results of this analysis for a.e.p. 30-busbar test system are included for illustration.
Keywords
monitoring; power system analysis computing; Newton Raphson methods; computer storage; data acquisition failures; fast decoupled load flow; metering inaccuracies; mode injections; power system real time monitoring; redundant line flows;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1977.0129