Title :
Voltage-transformer testing-set calibrator
Author :
Fiander, J.R. ; Smith, H.A.
Author_Institution :
Commonwealth Scientific and Industrial Research Organisation (CSIRO), National Measurement Laboratory, Sydney, Australia
fDate :
6/1/1975 12:00:00 AM
Abstract :
A direct-reading instrument for the precise calibration of voltage-transformer testing sets of the comparator type is described. The calibrator covers a range of ±11.11% for voltage error and ±411 min for phase error. These quantities are indicated on decade dials with constant resolutions of 0.001% and 0.1 min, respectively. The accuracy depends on the indicated voltage errors and phase errors, but is well within the resolution limits of most commercially available testing sets.
Keywords :
calibration; potential transformers; transformer testing; calibration; comparator type; direct reading instrument; voltage transformer testing sets;
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
DOI :
10.1049/piee.1975.0187