DocumentCode :
1440771
Title :
Electrothermal model for complete metal-oxide surge arresters
Author :
Da Costa, E. Guedes ; Naidu, S.R. ; De Lima, A. Guedes
Author_Institution :
Dept. of Electr. Eng., Univ. Fed. de Pernambuco, Brazil
Volume :
148
Issue :
1
fYear :
2001
fDate :
1/1/2001 12:00:00 AM
Firstpage :
29
Lastpage :
33
Abstract :
A computational electrothermal model for a complete metal-oxide surge arrester based on the implicit form of the finite-differences method is presented. The model is used to calculate the cooling curve after the application of overvoltages and the temperature variations during standard test. The model has been checked against experiments carried out on a test section and a complete surge arrester and the behaviour of a hypothetical surge arrester during standard tests simulated
Keywords :
arresters; cooling; finite difference methods; overvoltage; thermal analysis; zinc compounds; ZnO; ZnO surge arresters; computational electrothermal model; cooling curve calculation; finite-differences method; metal-oxide surge arresters; overvoltages; temperature variations;