DocumentCode
1440790
Title
Mechanism of interaction between electric arc and breaking chamber in low voltage current limiting circuit breakers
Author
Abri, Assadollah ; Kjellnäs, Stefan ; Nordgren, Robert ; Lindgren, Sven ; Bånghammar, Lars Å
Author_Institution
Asea Brown Boveri, Ludvika, Sweden
Volume
27
Issue
5
fYear
1991
Firstpage
841
Lastpage
848
Abstract
The authors survey different types of contact arrangements with simple, double, and quadruple arc interruption in current-limiting low-voltage protective switching devices. The influence of the arc commutation from moving contact arm to commutation bar is discussed. A new type of rapid electromagnet with a rotating armature is presented. The performance of the electromagnet was investigated by the finite element method. The same method was used to study the configuration of the arcing chamber and the influence of different parameters on the contact repulsion forces. The experiments were carried out with the help of a capacitor bank, and the results were measured by a data acquisition system
Keywords
arcs (electric); circuit breakers; LV current limiting circuit breakers; arc breaking chamber; arc commutation; capacitor bank; commutation bar; contact repulsion forces; data acquisition system; double arc interruption; finite element method; moving contact arm; protective switching devices; quadruple arc interruption; rapid electromagnet; rotating armature; simple arc interruption; switchgear; Commutation; Current limiters; Data acquisition; Electromagnets; IEC standards; Impedance; Industry Applications Society; Low voltage; Power system protection; Switchgear;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.90338
Filename
90338
Link To Document