Identifying Transformer Inrush Current Based on Normalized Grille Curve
Author
Ma, Jing ; Wang, Zengping ; Yang, Qixun ; Liu, Yilu
Author_Institution
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
588
Lastpage
595
Abstract
A novel algorithm for discrimination between inrush currents and internal fault currents by utilizing the normalized grille curve is proposed. First, the calculation method of the normalized grille curve is presented. Then, two schemes to discriminate the inrush currents from the internal faults in the time and frequency domains are, respectively, developed. A total of 268 experimental measurements have been tested on an YNd11-connected transformer. The results indicate that the proposed technique is able to reliably and accurately distinguish inrush currents from internal faults with easy implementation. Furthermore, the new method is not affected by the saturation of current transformers.
Keywords
current transformers; fault currents; power transformers; YNd11-connected transformer; current transformers; internal fault currents; normalized grille curve; transformer inrush current; Circuit faults; Current transformers; Frequency domain analysis; Power transformers; Surge protection; Surges; Time domain analysis; Inrush currents; internal faults; normalized grille curve; power transformer;