DocumentCode
1441857
Title
Mobile capacitor units or emergency loading of transformers in open delta
Author
Wolf, Herman B. ; Mattison, G. G.
Author_Institution
Duke Power Company, Charlotte, N. C.
Volume
62
Issue
2
fYear
1943
Firstpage
83
Lastpage
86
Abstract
Loading of closed delta banks of substation transformers to a point approaching safe thermal limit results in severe overloading of two transformers as well as decided unbalance in voltage and current when operated in open delta as a result of the failure of one transformer. By the use of mobile capacitor units with capacitors arranged in two unequal groups, the load on two transformers in open delta is reduced, regulation improved, voltage and current are balanced within operating limits, and with the aid of fans, the top oil temperatures — and consequently, the copper temperatures — are kept within safe limits. This permits proper loading of transformers in closed delta, a relatively short interruption to service or reduction in load upon failure of one transformer in a bank, and a reduction in number of transformers required for emergency use.
Keywords
Capacitance; Capacitors; Loading; Mobile communication; Oil insulation; Power transformer insulation; Reactive power;
fLanguage
English
Journal_Title
Electrical Engineering
Publisher
ieee
ISSN
0095-9197
Type
jour
DOI
10.1109/EE.1943.6435615
Filename
6435615